MCP cum PA Hooter in Mumbai

Cease Fire & Electrical Services LLP supplies, installs and maintains the MCP cum PA hooter for fire alarm and PA systems in Mumbai, for high-rise housing societies, office towers, hotels, hospitals and schools. An MCP cum PA hooter puts a manual call point, a fire alarm hooter and a PA speaker in one unit, so each floor has one place to raise the alarm, hear the alarm tone and hear evacuation announcements. It is usually fixed in staircase lobbies, where all three would otherwise sit side by side.
What each part does
Manual call point
Connected toFire alarm panel
What it doesLets a person raise the fire alarm
Hooter
Connected toFire alarm panel sounder circuit
What it doesGives the fire alarm tone automatically
PA speaker
Connected toPA amplifier line
What it doesPlays live or recorded announcements
After the alarm, staff can use the PA system to tell people which floors to leave and which stairs to use. IS 2189:2008 calls this emergency voice alarm communication.
Where the units are fixed
- Mounting height of the call point
- 1.4 m above the floor
- Maximum travel distance to a call point
- 30 m inside the building
- Preferred position
- Near the entry to staircases on each floor
- Minimum alarm sound level
- 65 dB(A), or 5 dB(A) above lasting background noise
- Number of sounders
- At least one for each fire compartment
Large floors and rooms behind closed doors may need extra hooters or speakers so the tone and announcements reach everyone.
What to tell us
- Fire alarm system
- Conventional or addressable, with the panel make and model
- PA system
- Existing amplifier and zone call station, or a new PA system
- Call point
- Break glass or push type
- Quantity
- Number of units and floors
Supply, installation and servicing
We supply units to suit your fire alarm panel and PA amplifier, wire the call point and hooter to the panel and the speaker to the PA line, and test all three parts on every floor before handover. Under our AMC, the call points, alarm tone and announcements are checked during quarterly visits and the annual service.
The Maharashtra ACMS covers the PA system along with the fire alarm panel, and FireSense IoT monitoring reports both to the owner and to us.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) that designs, installs and maintains fire alarm and PA systems.RF-93/ RD-95 One team for both systems
We supply fire alarm and PA equipment, so all three parts of each unit are wired and tested together.
Right part first time
We confirm panel and amplifier compatibility before you order.
Request a quote
Tell us the number of floors and units, and the makes of your fire alarm panel and PA amplifier if you are adding to an existing system. We will confirm the right units and send a quote.
Frequently asked questions
What is an MCP cum PA hooter?
It is a single unit with a manual call point, a fire alarm hooter and a PA speaker. It lets people raise the alarm, hear the alarm tone and hear announcements from one place on each floor.
Where are MCP cum PA hooters used?
Mostly in staircase lobbies of high-rise housing societies and office towers, and in hotels, hospitals and schools. One unit on each floor near the stairs is the usual layout.
What is the difference between an MCP cum hooter and an MCP cum PA hooter?
An MCP cum hooter has a call point and a hooter. An MCP cum PA hooter adds a PA speaker, so the same unit can carry voice announcements.
Can MCP cum PA hooters connect to my existing fire alarm and PA system?
Usually, if the call point and hooter suit your fire alarm panel and the speaker suits your PA amplifier. Share both makes and models and we will confirm.
Does the alarm still work if the PA system fails?
When the call point and hooter are wired to the fire alarm panel, they keep working without the PA system. Only the announcements need the PA amplifier.
Is the PA system monitored under ACMS?
Yes. The Maharashtra ACMS covers the PA system along with the fire alarm panel, and our FireSense IoT panel reports both to the owner and to us.