MCP cum Hooter for Fire Alarm Systems in Mumbai

A red wall unit combining a hooter grille above and a manual call point below

Cease Fire & Electrical Services LLP supplies, installs and maintains the MCP cum hooter for fire alarm systems in Mumbai, for housing societies, offices, shops, godowns, schools and factories. An MCP cum hooter puts a manual call point and an alarm hooter in one unit, so anyone who sees a fire can raise the alarm and the tone sounds from the same place. We help you choose between a panel-connected unit and a standalone unit, and test each one before handover.

Two kinds of MCP cum hooter

  1. Power

    From the fire alarm panel

    230 V AC mains, with a built-in standby battery

  2. What happens when pressed

    The panel raises the alarm across the building

    The unit sounds its own hooter

  3. Detectors

    Works with the building's detectors and other sounders

    Not linked to detectors

  4. Suits

    Housing societies, offices, hospitals, factories

    Small shops, godowns, clinics and small offices

Where a building needs automatic fire detection, a standalone unit works alongside the fire alarm system, not in place of it.

Where MCP cum hooters are fixed

The call point part follows the IS 2189:2008 siting rules for manual call points, and the hooter part follows its sounder rules.

Mounting height of the call point
1.4 m above the floor
Maximum travel distance to a call point
30 m inside the building
Preferred position
Near the entry to staircases on each floor
Minimum alarm sound level
65 dB(A), or 5 dB(A) above lasting background noise
Number of sounders
At least one for each fire compartment

A combined unit saves wall space and wiring where a call point and a hooter would sit side by side anyway, such as staircase lobbies.

What to tell us

System
Panel-connected (with panel make and model) or standalone
Call point
Break glass or push type
Quantity
Number of units and floors
Location
Indoor or outdoor, and the size of the area to cover

Supply, installation and servicing

We supply units to suit your system, fix them at the correct height near exits and staircases, wire them to the panel or mains supply, and test the call point and hooter before handover. Under our AMC, units are operated and checked during quarterly visits and the annual service, including standby batteries on standalone units.

Engineer testing a fire alarm call point in a school corridor

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) that designs, installs and maintains fire alarm systems.

  • Proven on fire alarm work

    Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.

  • Right part first time

    We confirm whether you need a panel-connected or standalone unit before you order.

Request a quote

Tell us whether the units will connect to a fire alarm panel or work on their own, the number of floors and units, and your panel make and model if you have one. We will confirm the right unit and send a quote.

Frequently asked questions

What is an MCP cum hooter?

It is a single unit with a manual call point and an alarm hooter. Pressing the call point sounds the fire alarm tone from the same unit.

Does an MCP cum hooter need a fire alarm panel?

Panel-connected units do, and they raise the alarm across the building. Standalone units run on 230 V mains with a built-in battery and sound only their own hooter.

Is a standalone MCP cum hooter enough for my building?

It can suit a small shop, godown or clinic. Larger buildings and those that need automatic detection need a full fire alarm system with detectors and a panel.

Where should an MCP cum hooter be installed?

Near exits and staircase entries on each floor, with the call point 1.4 m above the floor. Nobody should have to travel more than 30 m to reach one.

Can I get an MCP cum hooter with a push type call point?

Units come with break glass or push type call points. Tell us which you prefer and we will confirm what suits your system.

How is the standby battery in a standalone unit checked?

We check it under AMC during quarterly visits and the annual service, and replace it when it no longer holds charge.

Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.

Call +91 9920676281