Fire Alarm Response Indicator in Mumbai

A small white response indicator with a red lamp, fixed to the wall above a grey door

Cease Fire & Electrical Services LLP supplies, installs and maintains the response indicator for fire alarm systems in Mumbai, for offices, hotels, hospitals, data centres and housing societies. A response indicator is a small lamp fixed outside a room or near a hidden detector that lights up when that detector goes into alarm, so staff can find the fire without opening every door or ceiling panel. IS 2189:2008 calls for one at the entrance to each room or cabin where a floor has more than one, and for detectors hidden in false ceilings, false floors, shafts and tunnels.

Where response indicators are needed

Outside rooms and cabins on a floor with several enclosures
Staff see which room has the alarm from the corridor
Rooms that are often locked
The alarm can be confirmed before the door is opened
Below detectors in false ceilings
The ceiling detector cannot be seen from the floor
Next to detectors in false floors
Cable voids under floors are hidden from view
Shafts, plenums and cable tunnels
Detectors there are out of sight

IS 2189 notes that remote indicator lamps outside rooms make a zone easier to search, which cuts the need for many small zones on conventional systems.

How it works

The indicator is wired to the remote output of a detector. When the detector operates, its own LED lights and the response indicator lights at the same time. It uses little power and is fitted at a height where it can be seen, usually above or beside the door or directly below a concealed detector. Conventional and addressable detectors both have remote outputs, but the indicator must suit the detector's output.

What to tell us

Detectors
Detector make and model, and whether conventional or addressable
Locations
Rooms, false ceilings, false floors and shafts that need an indicator
Quantity
Number of indicators and floors
Mounting
Surface or flush, wall or ceiling

Supply, installation and servicing

We supply indicators to suit your detectors, fix them where they can be seen from the corridor or floor, wire them to the detector's remote output and test each one by operating its detector before handover. Under our AMC, indicators are checked whenever their detectors are tested during quarterly visits and the annual service.

Engineer testing a ceiling smoke detector with a pole tester in a hospital corridor

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) that designs, installs and maintains fire alarm systems.

  • Proven on detection work

    Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.

  • Right part first time

    We confirm detector compatibility before you order.

Request a quote

Tell us the detector make, the rooms and hidden spaces that need indicators, and the number of floors. We will confirm the right indicator and send a quote.

Frequently asked questions

What is a response indicator in a fire alarm system?

It is a small lamp wired to a detector that lights up when the detector goes into alarm. It is fixed where people can see it, such as outside a room or below a false ceiling.

Where are response indicators required?

IS 2189 calls for one at the entrance to each room or cabin where a floor has more than one enclosure. They are also needed for detectors hidden in false ceilings, false floors, shafts, plenums and tunnels.

Why does a detector above a false ceiling need a response indicator?

Nobody can see the detector's own LED from the floor. The indicator below it shows which ceiling void has the alarm, so staff know where to look.

Does a response indicator work with addressable detectors?

Yes, most addressable detectors have a remote output as well. The indicator must suit the detector's output, so share the detector make and model.

Does a response indicator raise the alarm itself?

No, it only shows that a detector has operated. The fire alarm panel raises the alarm and sounds the hooters.

Can response indicators be added to an existing system?

Yes, if the existing detectors have a remote output that suits the indicator. Share the detector make and model and we will confirm.

Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.

Call +91 9920676281