Rate of Rise Heat Detector in Mumbai

Three low white round heat detectors with vented domes, fixed to a concrete ceiling

Cease Fire & Electrical Services LLP supplies, installs and maintains the rate of rise heat detector for fire alarm systems in Mumbai, for stores, workshops, parking areas and other dusty or steamy spaces where smoke detectors would give false alarms. It raises the alarm when the temperature climbs unusually fast, typically about 6.7 °C to 8.3 °C per minute, whatever the starting temperature, so it responds sooner than a fixed temperature detector to a fast-growing fire. We supply conventional and addressable versions to suit your panel and test each one before handover.

How a rate of rise heat detector works

The detector compares how quickly its sensing element heats up against a set rate. A slow, steady rise, such as a room warming during the day, does not trigger it; a sudden climb does. Because a very slow fire may never cross the rate threshold, most models also include a fixed temperature element that operates at a set point. IS 2189 describes this combined detector as rate of rise cum fixed temperature.

  1. Operates when

    The temperature climbs faster than a set rate

    The air reaches a set temperature

  2. Speed on a fast-growing fire

    Faster

    Slower

  3. Rooms that heat up quickly in normal use

    Not suitable

    Suitable

  4. Rooms normally above about 43 °C

    Not suitable

    Suitable with the right rating

Where it is used

  • Stores, godowns and workshops
  • Parking areas and garages
  • Battery rooms and small storage areas, where IS 2189 recommends heat or flame detection
  • Dusty or steamy areas where a smoke detector would give false alarms
  • Avoid rate of rise detectors in kitchens, boiler rooms, DG set rooms and near ovens, where the temperature rises quickly in normal use. A fixed temperature detector suits those rooms. Escape routes and high-value areas need smoke detectors, which warn much earlier.

Spacing and mounting rules to know

Distance from any point to the nearest detector, flat ceiling up to 5 m high
Up to 5.3 m
Ceilings between 5 m and 7 m
Up to 3.5 m
Ceilings above 7 m
Heat detectors not to be used
Minimum number
At least one heat detector per 50 m²
Depth of the sensing element below the ceiling
25 mm to 150 mm

IS 2175 is the Indian product standard for heat sensitive fire detectors.

Supply, installation and servicing

We supply detectors with their bases, fix and wire them to the approved layout, and test each one before handover. On combined detectors, the rate of rise element is tested with a controlled heat source, taking care not to damage a non-resettable fixed temperature element, as IS 2189 advises. Under our AMC, detectors are checked during quarterly visits and the annual service.

Detector faults and panel status can be reported through FireSense IoT monitoring, which supports the ACMS now required for covered buildings in Maharashtra. See the ACMS guide.

Engineer testing a ceiling smoke detector with a pole tester in a hospital corridor

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) that designs, installs and maintains fire alarm systems.

  • Proven on detection work

    Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.

  • Right part first time

    We confirm the detector type and panel compatibility before you order.

Request a quote

Tell us the number of detectors, the rooms they are for, and your panel make and model if you are adding or replacing detectors. We will confirm the right type and send a quote.

Frequently asked questions

What is a rate of rise heat detector?

It is a fire detector that operates when the temperature around it climbs faster than a set rate. It responds to fast-growing fires sooner than a fixed temperature detector.

At what rate does a rate of rise heat detector activate?

Most operate at a rise of about 6.7 °C to 8.3 °C per minute, regardless of the starting temperature. The exact rate depends on the model.

Does a rate of rise detector also have a fixed temperature setting?

Most models combine both, so they also operate at a set temperature if a fire grows too slowly to trip the rate element. Check the data sheet, or ask us before you order.

Where should a rate of rise heat detector not be used?

Not in rooms where the temperature rises quickly in normal use, such as kitchens, boiler rooms and DG set rooms, or where it is normally above about 43 °C. Use a fixed temperature detector there.

Is a rate of rise heat detector better than a smoke detector?

No, they suit different places. Smoke detectors give much earlier warning in rooms and escape routes, and heat detectors are used where smoke detectors would give false alarms.

How many rate of rise heat detectors do I need?

IS 2189 allows up to 5.3 m from any point to the nearest heat detector under a flat ceiling up to 5 m high, with at least one per 50 m². We work out the number from your layout and ceiling height.

Can heat detector status be monitored remotely?

Yes. FireSense IoT monitoring reports fire alarm panel and detection status to the owner and to us, which supports the ACMS required for covered buildings in Maharashtra.

Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.