Sprinkler Annunciator Panel in Mumbai

Cease Fire & Electrical Services LLP supplies, installs and tests the sprinkler annunciator panel in Mumbai for residential towers, offices, hospitals, hotels and factories. A sprinkler annunciator panel takes the signals from the sprinkler flow switches and shows which floor or zone has water flowing, with a light for each zone and an alarm sounder. It is usually placed at the ground-floor fire control room or security desk, so staff know at once where to go.
What a sprinkler annunciator panel does
- One window or light per flow switch
- Shows exactly which floor or zone has water flow
- Panel buzzer and hooter output
- Sounds the alarm at the panel and on an external hooter
- Silence, reset and lamp test buttons
- Staff can silence the alarm, reset the panel after the event and check that every light works
- Potential-free contact
- Passes a common alarm signal to the fire alarm panel, building management system or fire pump room
- Battery back-up
- Keeps the panel working during a power cut
Annunciator panel or addressable fire alarm panel?
In buildings with a conventional or no fire alarm system, a separate sprinkler annunciator panel is the simple way to show flow switch alarms by zone. In buildings with an addressable fire alarm system, each flow switch can instead be connected to the fire alarm panel through a flow switch control module, and the fire alarm panel shows the location. We recommend the option that suits your building and existing system.
What to tell us
- Zones
- Number of flow switches or zones to show, with room for future zones
- Other inputs
- Tamper switches, pump running or other signals to display
- Outputs
- External hooter, link to the fire alarm panel or building management system
- Location
- Where the panel will be mounted, such as the fire control room or security desk
Supply, installation and servicing
We supply the panel with the flow switches and wiring, label every zone by floor or area, and connect the hooter and outputs. At commissioning we flow water through each zone's test and drain valve and check that the right zone lights up and the alarm sounds. During AMC visits we repeat the zone tests, run the lamp test and check the batteries.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) with 1,500+ projects.RF-93/ RD-95 Sprinklers and detection together
We have delivered sprinkler and fire detection packages together, such as Palkhi Roha, Kandivali East (G + 14).
One supplier
Annunciator panels, flow switches, valves and installation from one team.
Request a quote
Send your BOQ or drawings with the number of zones and any other signals to display. We will confirm the specification and quote.
Frequently asked questions
What is a sprinkler annunciator panel?
It is a panel that shows which floor or zone of a sprinkler system has water flowing. It receives signals from the flow switches and lights the matching zone while sounding an alarm.
Why do I need a sprinkler annunciator panel?
Without it, the sprinkler alarm tells you water is flowing but not where. The panel shows the exact floor or zone, so staff and the fire brigade reach the right place quickly.
Where should a sprinkler annunciator panel be installed?
At a place that is always staffed or easy to reach in a fire, usually the ground-floor fire control room or security desk.
What is the difference between a sprinkler annunciator panel and a fire alarm panel?
An annunciator panel only displays the signals from sprinkler flow switches and similar inputs. A fire alarm panel also runs smoke and heat detectors, manual call points and sounders across the building.
Does the annunciator panel work in a power cut?
Yes, when it has a battery back-up with a built-in charger, which most do. We check the batteries during AMC visits.
Can an annunciator panel be connected to the fire alarm system?
Yes. Its common alarm contact can signal the fire alarm panel or building management system, so a sprinkler alarm also shows there.
Can you add an annunciator panel to an existing sprinkler system?
Yes. We connect the existing flow switches, label each zone by floor or area and test every zone by flowing water through its test valve.
Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.