Cease Fire & Electrical Services LLP supplies, wires and tests the flow switch control module for sprinkler systems in Mumbai, in high-rise residential towers, offices, hospitals, hotels and factories with addressable fire alarm systems. A flow switch control module is an addressable module that connects a sprinkler flow switch, or a valve tamper switch, to the fire alarm panel's loop. When water flows, the panel shows an alarm with the exact floor or zone, and it reports a fault if the wiring to the switch is cut.

What the module does

Gives the switch an address
The panel identifies each flow switch by its own address and label, such as "Sprinkler flow, 7th floor"
Reports water flow
The flow switch contact closes and the module sends an alarm to the panel
Watches the wiring
An end-of-line resistor lets the module detect a broken or shorted cable and report a fault
Reports closed valves
Wired to a valve tamper switch, it sends a supervisory signal if a sprinkler control valve is closed

Where it is used

  • At the zone or floor control valve on each floor of a sprinkler riser
  • At the sprinkler alarm valve, for its pressure or flow switch
  • At isolation valves fitted with tamper switches
  • When an existing conventional flow switch is connected to a new addressable fire alarm panel

What to tell us

Fire alarm panel
Make and model; modules must be compatible with, and listed for, the panel they report to
Inputs
Number of flow switches and tamper switches to connect
Layout
Floors or zones, and where the switches are
Existing system
New installation, or connecting existing switches to a new panel

Supply, installation and servicing

We supply the modules with the flow switches and tamper switches, wire them on the loop, and programme a clear label for each address. At commissioning we open the test and drain valve on each zone to prove that water flow gives the right alarm at the panel, and we close each valve to check the supervisory signal. During AMC visits we repeat these tests and check the wiring and labels.

Engineer at a red sprinkler control valve with two pressure gauges in a basement car park

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) with 1,500+ projects.

  • Sprinklers and fire alarms in-house

    We install both systems, so flow switches, modules and panel are tested together.

  • Addressable experience

    Addressable fire alarm systems at 65 receiving substations for Adani Electricity Mumbai.

Request a quote

Send your BOQ or drawings with the fire alarm panel make and the number of flow and tamper switches. We will confirm the specification and quote.

Frequently asked questions

What is a flow switch control module?

It is an addressable module that connects a sprinkler flow switch to the fire alarm panel's loop. It tells the panel which flow switch has operated, so staff know which floor or zone has water flowing.

Why does a flow switch need a module?

A flow switch is a simple contact that cannot talk to an addressable panel on its own. The module gives it an address and watches its wiring for faults.

Can one module monitor a flow switch and a tamper switch?

It depends on the module. Some have one input and others have two or more, so we choose the module to suit how many switches are at each valve.

Where is the module installed?

Usually close to the flow switch at the floor or zone control valve, where it is easy to reach for testing.

Do I need a module if my fire alarm system is conventional?

No. In a conventional system the flow switch is wired to a zone on the fire alarm panel or to a sprinkler annunciator panel.

How is a flow switch control module tested?

We open the test and drain valve on the zone so water flows through the flow switch, then check that the panel shows the right alarm and location.

Have you installed addressable systems on large projects?

Yes. We installed addressable fire alarm systems at 65 receiving substations for Adani Electricity Mumbai. See the project page.