Fire Alarm Control Module in Mumbai

Cease Fire & Electrical Services LLP supplies, installs and programs the fire alarm control module for addressable fire alarm systems in Mumbai, for commercial towers, hospitals, hotels, malls, factories and high-rise housing societies. A control module is an addressable output device: when the panel detects a fire, it switches on sounders or sends a signal to shut down air handling units, bring lifts to the ground floor, start pressurisation fans or release doors. We wire and program each module to the building's cause and effect plan and test every action before handover.
Control module or relay module
Makers use different names, but addressable output modules come in two main types.
Output
Supervised control moduleSwitches a powered 24 V DC circuit
Relay modulePotential-free (dry) contacts
Power
Supervised control moduleUsually needs a separate 24 V supply for the load
Relay moduleNo power output
Supervision
Supervised control moduleChecks the circuit for open and short faults
Relay moduleUsually not supervised
Typical use
Supervised control moduleSounder and strobe circuits
Relay moduleSignals to AHUs, lifts, fans, dampers, access control and BMS
Both sit on the addressable loop and have their own address, so the panel can switch them one by one to suit the fire zone.
What a control module can operate
- Sounders and strobes
- Switched on by floor or zone
- Air handling units
- Shut down so they do not spread smoke
- Lifts
- Recalled to the ground floor
- Staircase pressurisation fans
- Started to keep smoke out of the stairs
- Smoke exhaust fans and dampers
- Started or opened to clear smoke
- Access-controlled doors
- Released so people can get out
- Gas supply
- Shut off, where a solenoid valve is fitted
Which actions run in a fire is set out in the building's cause and effect plan, and the panel is programmed to follow it.
What to tell us
- Panel
- Make and model of the addressable panel
- Outputs
- The list of services to control, per floor or zone
- Cause and effect
- Your cause and effect plan, if you have one
- Services
- Whether each service needs a powered output or a dry contact signal
Supply, installation and servicing
We supply modules to match your panel, fix them near the equipment they control, wire and address them, and program the panel to the cause and effect plan. Every output is then tested by setting off the alarm in each zone and checking that the right services respond. Under our AMC, these actions are checked during quarterly visits and the annual service.
FireSense IoT monitoring can also report the status of pressurisation and exhaust fans, which the control modules start in a fire, and supports the ACMS now required for covered buildings in Maharashtra.

Why choose Cease Fire
Since 1992
A Maharashtra Fire Services Licensed Agency (MFS/
LA/ ) that designs, installs and maintains fire alarm systems.RF-93/ RD-95 Proven on addressable work
Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.
Fire and electrical in one team
A Maharashtra Electrical Contractor (Licence No. 17545), so the links to AHU, lift and fan panels are handled by our own licensed team.
Request a quote
Tell us the panel make and model and the services you need the fire alarm to control, or send your cause and effect plan. We will confirm the modules needed and send a quote.
Frequently asked questions
What is a control module in a fire alarm system?
It is an addressable output device on the fire alarm loop. When the panel detects a fire, it switches on sounders or sends a signal to other building services such as AHUs, lifts and fans.
What is the difference between a control module and a relay module?
A supervised control module switches a powered 24 V circuit and checks the wiring for faults, and is used for sounders. A relay module gives dry contacts that signal other equipment, such as AHU shutdown or lift recall.
Why does the fire alarm need to shut down AHUs?
Air handling units can carry smoke through ducts to other floors. Shutting them down in a fire helps keep smoke out of escape routes.
What is a cause and effect plan?
It is a table that sets out which actions happen when each detector or zone goes into alarm. The panel is programmed to follow it, and every action is tested at handover.
Does a control module work with any fire alarm panel?
No, addressable modules must match the panel's make and protocol. Share the panel make and model and we will confirm a compatible module.
How is a control module tested?
The alarm is set off in each zone and each controlled service is checked, such as the AHU stopping or the lift returning to the ground floor. We do this at handover and during AMC visits.
Can the fire alarm start pressurisation and exhaust fans?
Yes. A control or relay module starts staircase pressurisation fans and smoke exhaust fans, and opens dampers, as set out in the cause and effect plan.