Fire Alarm Control Module in Mumbai

Two small white fire alarm modules, one with its cover off showing a circuit board and screw terminals

Cease Fire & Electrical Services LLP supplies, installs and programs the fire alarm control module for addressable fire alarm systems in Mumbai, for commercial towers, hospitals, hotels, malls, factories and high-rise housing societies. A control module is an addressable output device: when the panel detects a fire, it switches on sounders or sends a signal to shut down air handling units, bring lifts to the ground floor, start pressurisation fans or release doors. We wire and program each module to the building's cause and effect plan and test every action before handover.

Control module or relay module

Makers use different names, but addressable output modules come in two main types.

  1. Output

    Switches a powered 24 V DC circuit

    Potential-free (dry) contacts

  2. Power

    Usually needs a separate 24 V supply for the load

    No power output

  3. Supervision

    Checks the circuit for open and short faults

    Usually not supervised

  4. Typical use

    Sounder and strobe circuits

    Signals to AHUs, lifts, fans, dampers, access control and BMS

Both sit on the addressable loop and have their own address, so the panel can switch them one by one to suit the fire zone.

What a control module can operate

Sounders and strobes
Switched on by floor or zone
Air handling units
Shut down so they do not spread smoke
Lifts
Recalled to the ground floor
Staircase pressurisation fans
Started to keep smoke out of the stairs
Smoke exhaust fans and dampers
Started or opened to clear smoke
Access-controlled doors
Released so people can get out
Gas supply
Shut off, where a solenoid valve is fitted

Which actions run in a fire is set out in the building's cause and effect plan, and the panel is programmed to follow it.

What to tell us

Panel
Make and model of the addressable panel
Outputs
The list of services to control, per floor or zone
Cause and effect
Your cause and effect plan, if you have one
Services
Whether each service needs a powered output or a dry contact signal

Supply, installation and servicing

We supply modules to match your panel, fix them near the equipment they control, wire and address them, and program the panel to the cause and effect plan. Every output is then tested by setting off the alarm in each zone and checking that the right services respond. Under our AMC, these actions are checked during quarterly visits and the annual service.

FireSense IoT monitoring can also report the status of pressurisation and exhaust fans, which the control modules start in a fire, and supports the ACMS now required for covered buildings in Maharashtra.

Engineer testing a wall-mounted fire alarm control panel, with a manual call point and a smoke detector nearby

Why choose Cease Fire

  • Since 1992

    A Maharashtra Fire Services Licensed Agency (MFS/LA/RF-93/RD-95) that designs, installs and maintains fire alarm systems.

  • Proven on addressable work

    Addressable fire alarm systems at 65 Adani Electricity substations in Mumbai.

  • Fire and electrical in one team

    A Maharashtra Electrical Contractor (Licence No. 17545), so the links to AHU, lift and fan panels are handled by our own licensed team.

Request a quote

Tell us the panel make and model and the services you need the fire alarm to control, or send your cause and effect plan. We will confirm the modules needed and send a quote.

Frequently asked questions

What is a control module in a fire alarm system?

It is an addressable output device on the fire alarm loop. When the panel detects a fire, it switches on sounders or sends a signal to other building services such as AHUs, lifts and fans.

What is the difference between a control module and a relay module?

A supervised control module switches a powered 24 V circuit and checks the wiring for faults, and is used for sounders. A relay module gives dry contacts that signal other equipment, such as AHU shutdown or lift recall.

Why does the fire alarm need to shut down AHUs?

Air handling units can carry smoke through ducts to other floors. Shutting them down in a fire helps keep smoke out of escape routes.

What is a cause and effect plan?

It is a table that sets out which actions happen when each detector or zone goes into alarm. The panel is programmed to follow it, and every action is tested at handover.

Does a control module work with any fire alarm panel?

No, addressable modules must match the panel's make and protocol. Share the panel make and model and we will confirm a compatible module.

How is a control module tested?

The alarm is set off in each zone and each controlled service is checked, such as the AHU stopping or the lift returning to the ground floor. We do this at handover and during AMC visits.

Can the fire alarm start pressurisation and exhaust fans?

Yes. A control or relay module starts staircase pressurisation fans and smoke exhaust fans, and opens dampers, as set out in the cause and effect plan.

Question not answered here? Call our team, Monday to Saturday, 9 am to 7 pm.